S Range Shockproof Contactor Selection Guide |
![]() |
![]() |
![]() |
|||||
| Contactor | SA22 |
S030 |
S055 |
S090 |
S200 |
||
Ith open |
(A) |
60 |
70 |
130 |
200 |
400 |
|
AC 3 70OC |
440V |
(KW) |
|||||
(A) |
40 |
54 |
95 |
146 |
290 |
||
AC 3 80OC |
440V |
(KW) |
|||||
(A) |
35 |
48 |
84 |
130 |
257 |
||
Coil (Inrush) |
(VA) |
100 |
170 |
245 |
700 |
1500 |
|
Coil (Sealed) |
(VA) |
12 |
24 |
22 |
140 |
250 |
|
Mechanical Life (Million Operations) |
10 |
10 |
10 |
5 |
5 |
||
Max. Aux. Contacts |
3 N/O + 2 N/C |
4 C/O |
4 C/O |
7 |
7 |
||
Short Cct MAx. Fuse 32-50kA, Type 2 (* Note 1) |
80 |
125 |
200 |
315 |
450 |
||
Operating Time mS Energised |
8-14 |
14-27 |
16-32 |
35-50 |
55-95 |
||
Operating Time mS De-energised |
7-10 |
5-15 |
6-17 |
17-23 |
16-20 |
||
*Note 1 |
Notes
|
||||||