UCAN Contactor Selection Guide
|
|
|
||
| Contactor | UCA1N |
UCA7N |
UCA20N |
|
Rated Thermal Current Ith (8 Hour Duty @ 70oC |
(A) |
24 |
73 |
210 |
DOL Motor Starting (@ 440V 60Hz) |
(kW) |
11 |
37 |
112 |
Making Capacity @ 0.35 pF |
(A) |
300 |
840 |
2000 |
Breaking Capacity |
(A) |
250 |
700 |
1600 |
Coil (Inrush) |
(VA) |
260 |
415 |
970 |
Coil (Sealed) |
(VA) |
45 |
66 |
110 |
Mechanical Life AC3
(Million Operations) |
0.5 |
0.5 |
0.5 |
|
Aux. Contacts Rated Thermal Current
@ 440V |
6 |
6 |
6 |
|
Operating Time mS
Energised |
17 |
14 |
26 |
|
Operating Time mS
De-energised |
6.5 |
11.3 |
10 |
|
Shock Rating (g) (Note 1) |
12 |
12 |
12 |
|
| Min Operating Voltage -Pull In (% Coil Volts) |
83 |
83 |
83 |
|
Min Operating Voltage |
>10 & <65 |
>10 & <65 |
>10 & <65 |
|
Note 1 : Shock Tested on solid mounts. The contactor is rated to 30g when suitable shock mounts
are used. The auxiliary contacts are zero rated for shock.