Westmaster Contactor Selection Guide |
|
|
|
|
|
|
|
|||
| Contactor | UA11 |
UA22 |
U030 |
U055 |
U090 |
U200 |
U400 |
||
Ith open |
(A) |
32 |
60 |
70 |
130 |
200 |
400 |
730 |
|
AC1 |
(A) |
25 |
55 |
65 |
120 |
180 |
380 |
700 |
|
AC2 |
(A) |
22 |
44 |
60 |
105 |
170 |
330 |
650 |
|
AC 3 Duty
|
220V |
(KW) |
5.9 |
12.5 |
17 |
30 |
50 |
100 |
200 |
(A) |
22 |
44 |
60 |
101 |
168 |
325 |
626 |
||
415V *Note 1 |
(KW) |
11 |
22 |
30 |
55 |
90 |
184 |
400 |
|
(A) |
22 |
44 |
60 |
105 |
165 |
325 |
646 |
||
440V |
(KW) |
12.5 |
26 |
35 |
65 |
100 |
200 |
420 |
|
(A) |
22 |
44 |
60 |
105 |
162 |
321 |
646 |
||
550V |
(KW) |
9.5 |
15 |
27 |
37 |
90 |
200 |
400 |
|
(A) |
14.5 |
20 |
37 |
52 |
117 |
260 |
510 |
||
AC4 Duty
|
415V |
(KW) |
5.5 |
8 |
16 |
33 |
59 |
110 |
245 |
(A) |
11 |
15 |
30 |
60 |
105 |
200 |
425 |
||
440V |
(KW) |
6 |
8.5 |
17 |
35 |
60 |
125 |
260 |
|
(A) |
11.5 |
15 |
30 |
60 |
105 |
200 |
425 |
||
AC5a (Lamp) |
(A) |
19 |
39 |
54 |
95 |
153 |
300 |
580 |
|
AC5b (Lamp) |
(A) |
18 |
35 |
48 |
84 |
136 |
264 |
520 |
|
AC6b (Capacitor) |
(A) |
16 |
27 |
39 |
63 |
110 |
215 |
350 |
|
KVAr @415/440V |
11.5 |
19.3 |
28 |
45 |
78 |
155 |
255 |
||
Coil (Inrush) |
(VA) |
80 |
100 |
170 |
245 |
700 |
1500 |
3000 |
|
Coil (Sealed) |
(VA) |
12 |
12 |
24 |
22 |
140 |
250 |
420 |
|
Mechanical Life (Million Operations) |
10 |
10 |
10 |
10 |
5 |
5 |
3 |
||
Max. Aux. Contacts |
6 |
9 |
8 |
8 |
8 |
8 |
8 |
||
Short Cct MAx. Fuse 32-50kA, Type 2 (* Note 2) |
50 |
80 |
125 |
200 |
315 |
450 |
800 |
||
Operating Time mS Energised |
8—14 |
8-14 |
14-27 |
16-32 |
35-50 |
55-95 |
40-70 |
||
Operating Time mS De-energised |
7—10 |
7-10 |
5-15 |
6-17 |
17-23 |
16-20 |
18-25 |
||
*Note 1 *Note 2 |
Notes
|
||||||||